Abstract
HTA Burgdorfâs PV laboratory has carried out many tests with small
grid-connected PV-inverters since 1989. In spring 1994, a new test
centre for PV-systems with a PV generator of 60 kWp became operational.
With this test centre, tests of medium sized inverters up to 30kW
are also possible. A significant extension of the testing facilities
was possible with the introduction of solar generator simulators.
Several PV generator simulators up to 25kW with high stability were
developed in 1998 to 2000 (one of them computer controlled). With
these simulators, partly automatic inverter tests can now be carried
out much faster. In this paper at first a short overview of the concepts
used in grid connected PV inverters is given. Then the most important
test results of all inverters tested (more than 28) will be displayed,
which clearly shows the considerable progress achieved in the last
years. The evolution of different important properties of PV inverters
will also be discussed. Results of intense tests of some recently
developed inverters used in many grid connected PV-systems will be
used to illustrate some interesting cases or typical performance
of new inverters. Reliability of inverters will considered using
monitoring data of more than 45 PV plants continuously monitored
since 1992